PLC outputs are the machine's hands — commands that energise contactors, open solenoids, start drives and light indicators. When an output fault occurs, the machine either fails to actuate or does the wrong thing. This guide covers a structured approach.
A structure for output faults
- Is the PLC commanding the output? Check the logic status and the rung driving it.
- Is the output status physically present? Does the output LED light, and is there voltage at the terminal?
- Is the field device being driven? Is the contactor pulling in, the solenoid shifting, the drive receiving its run command?
- Are permissives or interlocks holding the output off? A rung may be conditioned by a safety or sequence interlock.
- Is the field device healthy? Coil, solenoid, drive command wiring.
Common output types
- Relay outputs — driving contactors, solenoids, indicators. Watch for welded or worn relay contacts.
- Transistor outputs — fast switching, often driving VFD/servo command signals or indicators.
- Analog outputs — speed or position references to drives; check for scaling and signal health.
An illustrative diagnostic flow
- START — device does not actuate
- ↓ Is the logic energising the output? → No → check the rung, conditions and mode
- ↓ Yes → Is the output LED on? → No → possible output card fault or configuration
- ↓ Yes → Is voltage present at the terminal? → No → fuse/blown output
- ↓ Yes → Is the field device receiving it? → No → wiring/connector
- ↓ Yes → Is the field device itself healthy? → No → replace coil/solenoid/drive-side
- ↓ Capture and document the cause
Key points
- Separate "the PLC is not commanding" from "the PLC is commanding but nothing happens" — they point to completely different areas.
- Test the output, the field device and the wiring; do not assume the card.
- Some PLC brands are compatible with specific field devices and some are not — do not assume interoperability without checking the manufacturer documentation.